REPLACEMENT OF INDOOR COIL OF 4 TR FLOOR STANDING AC & OVERHAULING OF COMPRESSOR INSTALLED AT UPS ROOM GROUND FLOOR MAIN BUILDING, STATE BANK OF PAKISTAN, KARACHI

SBP BSC - Engineering Department (SBP Banking Services Corporation (BSC))

Reference: P178635

Tender information

Published
Submission deadline
Not specified
Procurement method
Request for Quotation
Procuring agency
SBP BSC - Engineering Department (SBP Banking Services Corporation (BSC))

Tender description

  • REPLACEMENT OF INDOOR COIL OF 4 TR FLOOR STANDING AC & OVERHAULING OF COMPRESSOR INSTALLED AT UPS ROOM GROUND FLOOR MAIN BUILDING, STATE BANK OF PAKISTAN, KARACHI
  • Replacement, testing & commissioning of an Indoor coil for 4 TR floor standing AC unit
  • Overhauling and restoration of a 4 TR scroll compressor

Technical Specifications

REPLACEMENT OF INDOOR COIL OF 4 TR FLOOR STANDING AC & OVERHAULING OF COMPRESSOR INSTALLED AT UPS ROOM GROUND FLOOR MAIN BUILDING, STATE BANK OF PAKISTAN, KARACHI — Replacement, testing & commissioning of an Indoor coil for 4 TR floor standing AC unit

Specification
Replacement, testing & commissioning of an Indoor coil for 4 TR floor standing AC unit, with specified technical requirements.
Specification
Make: Orient. Total Coil Face Area: 4.4 Sq. Ft. Heat Transfer Medium: Refrigerant Gas Tube Material: Copper Tube Size: 3/8 inch diameter. Copper Tubes: 26 SWG, high-quality seamless copper tubing. Number of Rows: 03. Fin Density: 16 FPI (Aluminum Fins). Fins Material: Aluminum Fins Coating: epoxy-coated for corrosive environments Fins: Blue/Gold Hydrophilic Protective Coated Aluminum Fins Side Plates: 2 mm thick Epoxy-Coated on Galvanized Iron (GI).
Specification
The scope of work shall include dismantling of defective indoor coil and supply & installation of a new coil in accordance with specified technical requirements. The work shall also include brazing of refrigerant piping connections, pressure testing using dry nitrogen, evacuation of the refrigerant circuit, performance testing, commissioning & restoration of AC unit to proper & satisfactory operating condition.
Specification
Note: Contractor must visit the site to check Sample available with the bank. In case of Minor Deviations in Sizing, Sample provided by Bank shall prevail
Specification
The work shall be executed in accordance with relevant HVAC standards, manufacturer's recommendations. Complete in all respects per direction of engineer incharge.

REPLACEMENT OF INDOOR COIL OF 4 TR FLOOR STANDING AC & OVERHAULING OF COMPRESSOR INSTALLED AT UPS ROOM GROUND FLOOR MAIN BUILDING, STATE BANK OF PAKISTAN, KARACHI — Overhauling and restoration of a 4 TR scroll compressor

Specification
Overhauling and restoration of a 4 TR scroll compressor fitted in a floor-mounted split air-conditioning system located at the UPS Room, comprising provision and installation of new compressor shaft seals and lubrication pump assembly. The work also includes replenishment with fresh compressor oil after necessary service. Complete in all respect as per directed by engineer incharge.

Official source